Fire Rated Sliding Doors: Tests, Classes and Where They Are Allowed

CommercialPublished By BDF Architectural

Yes, a sliding door can be fire rated. A fire rated sliding door is a complete sliding doorset (leaf, track, frame, glass, seals, closing mechanism and any motor) fire tested to BS EN 1634-1 and classified to BS EN 13501-2, for example E30, EI30 or EI60, with Sa for smoke control and C for self-closing. Sliding fire doors can be manual or automatic, glazed or solid. The harder question is usually where the door sits. Approved Document B writes its escape route guidance around doors that swing, and sets specific rules for automatic doors and for fire doors held open in everyday use. This guide covers the tests, classes, rules, alarm release, maintenance, fire shutters and what to send for a quote.

Fire rated sliding doors at a glance
Fire rated sliding door
What it isA sliding doorset tested and classified as one assembly to resist fire when closed
Fire testBS EN 1634-1, with smoke leakage tested to BS EN 1634-3
ClassificationBS EN 13501-2: E or EI (EI1 or EI2) plus minutes, such as E30 or EI60; Sa or S200 for smoke; C for self-closing
Older UK ratingFD30, FD60 and so on from a BS 476-22 test, with S for smoke; removed from Approved Document B from 2 September 2029
Rating neededSet by the fire strategy, using Approved Document B Table C1 (for example E30 Sa for a protected stairway door)
On escape routesAutomatic doors must fail safe or have a swing door beside them; the guidance on manual escape doors is written for doors that swing
Held open in daily useAllowed on an automatic release linked to the fire detection and alarm system
MaintenanceThe responsible person must keep fire safety equipment in efficient working order and good repair

What is a fire rated sliding door?

A fire rated sliding door is a fire doorset whose leaf slides along a track instead of swinging on hinges. Approved Document B defines a fire doorset as "a door or shutter which, together with its frame and furniture as installed in a building, is intended (when closed) to resist the spread of fire and/or gaseous products of combustion and meets specified performance criteria to those ends". Note the words "when closed". A sliding fire door that stands open in everyday use only protects the opening once it has shut, so the way it closes matters as much as its rating.

Manual and automatic sliding fire doors

A manual sliding fire door is opened by hand. It still needs a way of closing itself in a fire, and that closing mechanism is part of the tested assembly. An automatic sliding fire door runs on a motorised operator in everyday use, like an ordinary automatic entrance door, and has to behave as a fire door when the fire alarm or a detector signals it. Because the leaf is power operated, it also has to be safe for the people using it: BS EN 16005 covers the safety in use of power operated pedestrian doorsets, including sliding ones, and deals with people being struck or trapped by moving leaves.

Glazed and solid sliding fire doors

Glazed sliding fire doors use fire-resistant glass in a steel or aluminium frame to keep light and sightlines through a lobby, shop floor or corridor. As with any fire rated glazing, the glass is only rated in the frame, seals and fixings it was tested with. For example, the manufacturer Jansen lists a Janisol 2 fire-resistant sliding door as tested to EN 1634-1, class EI30. Solid sliding fire doors are used where light is not needed, such as large openings in warehouses and plant areas.

How sliding fire doors are tested: BS EN 1634-1

BS EN 1634-1 is the fire resistance test for door and shutter assemblies and openable windows. Its scope lists hinged and pivoted doors, horizontally and vertically sliding doors, folding and sliding folding doors, tilting doors and rolling shutters, so a sliding door is tested by the same method as a hinged one: built into a wall on a furnace and heated from one side while its integrity, and insulation if classified, is measured. Approved Document B asks for test exposure from each side separately (paragraph C3).

Smoke leakage at ambient temperature is tested to BS EN 1634-3, and BS EN 16034 is the product standard for doorsets with fire resisting and smoke control characteristics. The classification only covers what was tested or formally assessed: leaf sizes, glass, track, seals, hardware, operator and wall type. Approved Document B (paragraph C4) says test evidence should be "applicable to the complete installed assembly", because "small differences in detail may significantly affect the rating".

Fire ratings for sliding doors: E, EI, Sa and C classes

Test results are turned into a classification under BS EN 13501-2. The classes for fire doors and shutters, including those with glazing and hardware, are set out in Commission Decision 2000/367/EC. They are E or EI for 15, 20, 30, 45, 60, 90, 120, 180 or 240 minutes, or EW for 20, 30 or 60 minutes. Approved Document B states its requirement for fire doorsets in terms of integrity (E) for a period of minutes, with Sa added where restricted smoke leakage at ambient temperatures is needed.

What each part of a sliding fire door rating means
ClassWhat it meansExample
EIntegrity: the door stops flames and hot gases passing through for the stated minutesE30, E60
EI1 or EI2Integrity and insulation: the protected face also stays below a temperature limit. The 1 or 2 shows which definition of insulation was usedEI2 30, EI1 60
EWIntegrity with limited heat radiation through the doorEW30
SaRestricted smoke leakage at ambient temperature, tested to BS EN 1634-3. This is what Approved Document B asks forE30 Sa
S200The other smoke control class in BS EN 13501-2, given when different test conditions are metE30 S200
C (C0 to C5)The door passed the self-closing test. A digit from 0 to 5 can be added for the use categoryEI30 Sa C5
FD30, FD30SOlder UK rating from a BS 476-22 test: integrity in minutes, S for restricted smoke leakageFD30S

BS 476-22 and FD ratings

Many UK schedules still say FD30 or FD30S, the integrity rating from the older BS 476-22 test. Approved Document B Table C1 currently gives a European and a BS 476-22 figure for each door position, noting that national classifications do not necessarily equate with European ones. The 2029 amendment, effective from 2 September 2029, removes the BS 476-22 column: fire doorsets are then classified to BS EN 13501-2 or assessed as capable of meeting a classification. Our guide to fire door ratings covers the two systems and the 2029 change in more detail.

Where fire rated sliding doors are used

Sliding fire doors are chosen where an opening is too wide for a hinged leaf, or where a swinging leaf would block a shop floor, corridor or loading route:

  • Shops and shopping centres: wide openings between sales floors, stock rooms and service areas on a compartment line, often glazed so the opening still looks open
  • Offices: lobbies, reception areas and open-plan floors where a compartment wall crosses a wide opening
  • Hospitals and care buildings: wide openings for beds and trolleys in walls that also need to hold back fire and smoke
  • Warehouses and industrial buildings: large solid sliding doors on compartment walls between storage areas

In fire strategy terms they sit in compartment walls or in the enclosures of escape routes. Approved Document B Volume 2 Table C1 sets the minimum rating by position: a door in a compartment wall generally takes the period of the wall; doors to a protected stairway, or to a protected lobby or corridor leading to one, are E30 Sa; doors sub-dividing corridors that connect alternative exits are E20 Sa. Wide sliding doors also meet paragraph C8: unless a door gives both integrity and insulation, door openings should make up no more than 25% of a compartment wall's length, or more where a clear space can be kept on both sides. An EI door, or a fire rated glazed screen with a narrower door, can solve this.

Approved Document B: sliding and automatic doors on escape routes

Approved Document B gives the guidance for England in two volumes: Volume 1 for dwellings, including blocks of flats, and Volume 2 for all other buildings. The guidance on doors on escape routes is paragraphs 5.6 to 5.15 of Volume 2, with the same guidance for blocks of flats in paragraphs 3.93 to 3.101 of Volume 1 (which do not apply to flat entrance doors). The main points are:

  • Doors should be readily openable to avoid undue delay to people escaping (Vol 2, 5.6)
  • Fastenings should be simple and keyless from the escape side; electrically powered locks should unlock on the fire alarm, on power failure or from an override, a Type A call point as described in BS 7273-4 (5.7, 5.8)
  • In shop, commercial and assembly buildings, escape doors from rooms with more than 60 people should have either no locks, latches or bolts, or panic fastenings to BS EN 1125 (5.9)
  • Doors should open in the direction of escape whenever reasonably practicable, and always for more than 60 people or a very high fire risk (5.11)
  • Doors should open by at least 90 degrees, with a swing clear of level changes that does not reduce escape width (5.12)

Neither volume mentions manually operated sliding doors, and the opening and swing rules are written for hinged doors. A manual sliding door across an escape route therefore falls outside the standard guidance and needs to be justified in the fire strategy and accepted by building control. Two ways round this are to keep it off the escape route, or to provide a hinged escape door beside or within it; Jansen, for example, lists its Janisol 2 fire-resistant sliding door with or without an emergency exit function to EN 1125 or EN 179.

Automatic doors across escape routes

For powered doors, Approved Document B is specific. Volume 2 paragraph 5.15 (and Volume 1 paragraph 3.101) says that where revolving doors, automatic doors and turnstiles are placed across escape routes, they should either be automatic doors of the required width that fail safe, or have non-automatic swing doors of the required width immediately next to them. To count as failing safe, the door must meet one of three conditions:

  • Its failsafe system provides outward opening from any open position
  • It has a monitored failsafe system to open the doors if the mains electricity supply fails
  • It fails safe to the open position if the power fails

This is where an automatic sliding fire door needs care: as an escape door it is expected to fail open, and as a fire door to close. Approved Document B does not say how one door should do both, so the fire strategy decides, door by door, and the system must be tested and set up to match. A swing door of the required width beside the automatic door avoids the conflict. Our commercial doors guide covers automatic entrance doors that are not fire rated.

Hold-open devices and release on the fire alarm

Approved Document B (paragraph C5) says all fire doorsets should have a self-closing device. The exceptions are fire doorsets to cupboards, to service ducts normally locked shut, and within flats and dwellinghouses. Where a self-closing device would interfere with the normal use of the building, paragraph C6 allows self-closing fire doors to be held open by one of three things:

  • A fusible link, but not where the doorset is in an opening provided as a means of escape, unless it meets paragraph C7 (two fire doorsets in the same opening)
  • An automatic release mechanism activated by an automatic fire detection and alarm system
  • A door closer delay device

A sliding fire door that stands open during the day usually takes the second option: it is released to close when the fire alarm operates, and is marked "Automatic fire door keep clear" (paragraph C11). Where any part of BS 7273 applies to a fire alarm triggering another system, it should be followed (paragraph 1.17). BS 7273-4 covers the design, installation, commissioning and maintenance of the electrical controls that release held-open fire-resisting doors, unlock locked doors or cause powered sliding doors to open. It does not say whether such mechanisms should be used; that is for the fire strategy.

Fire rated sliding door or fire shutter?

Both are fire doorsets in Approved Document B's definition ("a door or shutter") and both are tested to BS EN 1634-1. A sliding fire door is a door people walk through; a rolling fire shutter stays open above the opening and only closes in a fire. Approved Document B paragraph C9 says rolling shutters should be capable of manual opening and closing for firefighting, and that shutters across a means of escape should only be released by a heat sensor, such as a fusible link, in the immediate vicinity of the door, not by smoke detectors or a fire alarm system unless the shutter also forms part of a smoke reservoir boundary.

Fire rated sliding door, fire shutter or hinged fire door in a glazed screen
Sliding fire doorFire shutter (rolling)Hinged fire door in a glazed screen
Everyday useA working door, manual or automaticNormally open; closes only in a fireA working door
Fire testBS EN 1634-1BS EN 1634-1Door BS EN 1634-1; screen BS EN 1364-1
Release in a fireSelf-closing; may be held open on an automatic release linked to the fire alarmAcross a means of escape: heat sensor near the door only, not the fire alarmSelf-closing; may be held open on an automatic release linked to the fire alarm
Light and viewYes, if glazedUsually noneYes
Escape routesOutside the standard guidance if manual; automatic doors must fail safe or have a swing door beside themMust not close on escape routes from a smoke detector or alarm signalFits the standard guidance on direction and swing

Where the aim is a wide, light-filled opening on a fire line that people also escape through, a fire rated glazed screen with a hinged glazed fire door set into it is often simpler to approve than a sliding door. The door fits the standard escape route guidance, and the glass keeps the opening feeling open.

Inspection and maintenance of sliding fire doors

In England and Wales, article 17 of the Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to keep fire safety facilities, equipment and devices "subject to a suitable system of maintenance" and "in efficient working order and in good repair". For new work, Approved Document B's guidance on Regulation 38 asks for fire safety information to be handed over, including as-built plans showing fire doorsets and specifications of fire safety equipment with routine maintenance schedules.

A sliding fire door has more moving parts than a hinged one, so routine checks typically cover:

  • The door closes fully and on its own from the fully open position, with nothing in the track or the closing path
  • The release works when the fire alarm is tested, and the door is not wedged or blocked open
  • Intumescent and smoke seals, gaskets and glazing beads are present and undamaged
  • Glass is undamaged and still the marked fire-resistant product originally fitted
  • On automatic doors, the operator, sensors and failsafe behaviour work as the fire strategy intends
  • Signs such as "Automatic fire door keep clear" are in place on both sides

Fire rated sliding doors in houses and flats

In a house, Approved Document B Volume 1 Table C1 asks for E20 doors to a protected stairway and in other fire resisting construction, and E30 Sa between the house and a garage. Where a loft conversion adds a storey above 4.5 m, fire resisting doors (minimum E20) and partitions should be provided on the escape route. Fire doorsets within flats and houses do not need self-closers. Volume 1 does not mention sliding doors. An ordinary sliding or pocket door has no fire rating, so a sliding door only counts if it is a doorset with test evidence for that configuration. Check with your building control body first.

What to send for a fire rated sliding door quote

  • The structural opening size (width and height) and the type of wall it sits in
  • The fire rating the fire strategy needs for that door, such as E30 Sa, EI30 or EI60
  • Whether the door is manual or automatic, and whether it is on an escape route, and in which direction people escape
  • Glazed or solid, and any glass type, vision or privacy requirement
  • How the door should behave on the fire alarm: held open and released, or kept closed
  • Locking, access control and any panic or emergency exit hardware
  • Drawings: plans and elevations, the door schedule and the fire strategy, plus programme dates

BDF Architectural supplies and installs glazed fire rated doors in aluminium and steel, including Jansen Janisol 2 steel doors tested to EI30, and fire rated glazed screens and partitions, as part of our wider fire rated glazing range. The rating for each door is set by the fire strategy and confirmed at technical review against the system's test evidence. If your schedule includes sliding or automatic fire doors, tell us and we will confirm whether a tested system covers them. Our commercial capability page sets out how we work with main contractors and architects.

Frequently asked questions

Can a sliding door be a fire door?

Yes. BS EN 1634-1, the fire resistance test for doors, covers horizontally and vertically sliding doors as well as hinged ones. A sliding door is a fire door when the complete doorset, including its leaf, track, frame, glass, seals and closing mechanism, has been tested and classified to BS EN 13501-2, for example as E30 Sa or EI30, and is installed as tested.

Are fire rated sliding doors allowed on escape routes?

Automatic doors are, if they meet Approved Document B paragraph 5.15: they must be of the required width and fail safe (opening outwards from any position, opening on a monitored failsafe if the mains supply fails, or failing to the open position), or have a non-automatic swing door of the required width immediately beside them. Approved Document B has no guidance on manually operated sliding doors on escape routes, so a manual sliding door there needs to be justified in the fire strategy and accepted by building control.

What happens to an automatic fire rated sliding door when the fire alarm goes off?

It does what the fire strategy says it should for that position. A fire door held open in everyday use can be released by an automatic mechanism linked to the fire detection and alarm system so that it closes. An automatic door across an escape route is expected to fail safe, or to have a swing door beside it. BS 7273-4 covers the control arrangements that release held-open fire doors, unlock locked doors or make powered sliding doors open.

Can you get fire rated sliding glass doors?

Yes. Glazed sliding fire doors use fire-resistant glass in a steel or aluminium frame and are tested and classified as a complete doorset, often to E30 or EI30. The glass is only rated in the frame, seals and fixings it was tested with. Approved Document B Table B3 limits uninsulated (integrity-only) glazing in doors and walls on escape routes, so insulating EI glass is used where those limits would otherwise be exceeded.

Can I use a fire rated sliding door in a house?

Approved Document B Volume 1 asks for E20 fire doors to the protected stairway of a house and in a loft conversion adding a storey above 4.5 m, and E30 Sa between a house and an integral garage. It does not mention sliding doors. An ordinary sliding or pocket door has no fire rating, so a sliding door only counts if it is a fire doorset with test evidence for that configuration. Check with your building control body first.

Do fire rated sliding doors need to be insulated (EI)?

Not always. Approved Document B sets fire door ratings in terms of integrity, such as E30 Sa. But fire doorsets often give little insulation, so unless a door gives both integrity and insulation, door openings should make up no more than 25% of the length of a compartment wall. Wide sliding doors on a compartment line can therefore need an EI rating, and the fire strategy decides.

What is the difference between a fire rated sliding door and a fire shutter?

Both are fire doorsets tested to BS EN 1634-1. A sliding fire door is a working door that people use, and it can be held open and released by the fire alarm. A rolling fire shutter stays open and only closes in a fire. Approved Document B says shutters across a means of escape should only be released by a heat sensor near the door, not by smoke detectors or the fire alarm, unless the shutter forms part of a smoke reservoir boundary.

How often should sliding fire doors be checked?

The Regulatory Reform (Fire Safety) Order 2005 does not set a fixed interval. The responsible person must keep fire safety equipment in efficient working order and good repair under a suitable system of maintenance, and the fire safety information handed over with the building should include routine maintenance schedules. Checks normally cover closing from fully open, the release on the fire alarm, seals, glass and the track.