Specification Guide

Fire Door Ratings Explained: FD30 to FD120, E30 Sa, EI30 and the 2029 Change

CommercialPublished By BDF Architectural

A fire door rating tells you how long a tested doorset held back fire and which criteria it met. FD30 is the British Standard (BS 476-22) rating for 30 minutes of integrity, E30 is the European (BS EN 13501-2) class for the same criterion, EI adds insulation and Sa adds smoke control. In England, Table C1 of Approved Document B sets the minimum integrity rating for each door position, and from 2 September 2029 it gives European classes only. This guide explains each rating, how the two systems compare, what Table C1 asks for, how glass affects a fire door, and what to check when you specify or maintain fire rated doors. For the glass classes themselves, see our guide to E, EW and EI fire rated glazing.

Fire door ratings at a glance

Fire door ratings and where Approved Document B uses them (the fire strategy sets each door)
RatingWhat it meansTypical use in Approved Document B
FD20 / E2020 minutes of integrityProtected entrance hall or landing in a flat; protected stair in a house (Table C1 items 9, 11)
FD20S / E20 Sa20 minutes of integrity plus cold smoke controlDoors sub-dividing corridors or closing off dead ends; other protected corridors (items 5b, 7)
FD30 / E3030 minutes of integrityDoors to an external escape route, in a cavity barrier, to a place of special fire hazard, or to a lift shaft that is not a protected shaft (items 4b, 6, 8, 10)
FD30S / E30 Sa30 minutes of integrity plus cold smoke controlProtected stairs and their lobbies or corridors, lift lobbies, flat entrance doors onto common areas (items 2a, 2b, 4a, 5a, 5c)
FD60 / E6060 minutes of integrityA compartment wall separating buildings (minimum 60), or a 60 minute compartment wall (items 1, 2e)
FD90, FD120 / E90, E12090 or 120 minutes of integrityCompartment walls or floors needing 90 or 120 minutes under Table B2 (items 1, 2e, 3)
EI30, EI60 and upIntegrity plus insulationWhere the fire strategy needs it, or where uninsulated doors would exceed 25% of a compartment wall's length (para C8)

What FD30, FD60, FD90 and FD120 mean (BS 476-22)

FD ratings come from BS 476-22, the British Standard fire resistance test for non-loadbearing elements. FD means fire door, and the number is how many minutes the doorset kept its integrity, stopping flames and hot gases getting through. An S suffix, as in FD30S, means it also restricts cold smoke: Approved Document B links this to no more than 3 m³ per metre per hour of leakage, from the head and jambs, at 25 Pa under BS 476-31.1. An FD rating says nothing about insulation, so an FD60 door can get hot on the protected side and still pass. Approved Document B asks for doorsets to be tested from each side separately (lift doors from the landing side only).

What E, EW, EI, Sa, S200 and C mean (BS EN 13501-2)

European classes are given under BS EN 13501-2 after a fire resistance test to BS EN 1634-1 and, for smoke control, a leakage test to BS EN 1634-3. The letters show which criteria the doorset met; the number shows for how many minutes:

  • E: integrity. The same criterion as FD, from a different test
  • EW: integrity plus a limit on heat radiated from the protected face (door classes EW20, EW30, EW60)
  • EI1 or EI2: integrity plus insulation, limiting the temperature rise on the protected face. The 1 or 2 shows which of the standard's two definitions of insulation was used
  • Sa: restricted smoke leakage at ambient temperature (cold smoke). This is the suffix Approved Document B uses
  • S200: restricted smoke leakage at ambient temperature and at a medium temperature of 200 °C
  • C: passed the self-closing test, sometimes followed by a digit from 0 to 5 for the use category

E and EI door classes run from 15 to 240 minutes. Read the whole classification, not just the first letters: a door classified for insulation, smoke and self-closing tells you far more than one classified for integrity alone.

FD30 vs E30 and EI30: how the two systems compare

The two systems line up by criterion, not by test. Approved Document B's current Table C1 puts them side by side, so where the European column asks for E30 Sa the British Standard column asks for FD30S. But the table's own note says national classifications do not necessarily equate with European ones, and a product cannot normally claim a European class unless it has been tested for it. In practice:

  • FD30 and E30 both mean 30 minutes of integrity, but an FD30 test report does not make a door E30
  • EI30 is a higher level than FD30 or E30, because it adds insulation, which no FD rating covers
  • FD30S and E30 Sa both mean cold smoke control, measured by different tests (BS 476-31.1 and BS EN 1634-3)

Both tests heat the door on the same time-temperature curve, but the furnace pressure conditions differ, and trade guidance on the change (for example from the British Woodworking Federation's Fire Door Alliance) says the European test is generally the more onerous for doors. Approved Document B also says relevant test evidence is unlikely to come from test standards with different classification criteria, so a BS 476-22 result cannot simply be relabelled as a European class.

What Approved Document B Table C1 asks for

Table C1, "Provisions for fire doorsets", is the same in Volume 1 (dwellings) and Volume 2 (buildings other than dwellings). Every rating is for integrity (E) in minutes, with Sa where cold smoke must be restricted; doors needing Sa can instead rely on pressurisation to BS EN 12101-6. The current table, which applies until 1 September 2029, reads:

Approved Document B Table C1: minimum fire resistance of fire doorsets (integrity, minutes)
Position of door (item)European classBS 476-22 (to 1 Sept 2029)
1. Compartment wall separating buildingsAs the wall, minimum 60As the wall, minimum 60
2a. Compartment wall between a flat and a space in common useE30 SaFD30S
2b. Compartment wall enclosing a protected stair or evacuation shaft (wholly or partly above ground) in flats, other residential, assembly and recreation, or office buildingsE30 SaFD30S
2c. Compartment wall enclosing any other protected stair or evacuation shaftHalf the wall's period, minimum 30, with SaHalf the wall's period, minimum 30, with S
2d. Compartment wall enclosing a lift or service shaftHalf the wall's period, minimum 30Half the wall's period, minimum 30
2e. Any other compartment wallAs the wall; add Sa for progressive horizontal evacuationAs the wall; add S for progressive horizontal evacuation
3. Compartment floorAs the floorAs the floor
4a. Enclosure of a protected stairway or evacuation shaftE30 SaFD30S
4b. Enclosure of a lift shaft that is not a protected shaftE30FD30
5a. Protected lobby or corridor to a stair or evacuation shaftE30 SaFD30S
5b. Any other protected corridorE20 SaFD20S
5c. Protected lobby to a lift shaftE30 SaFD30S
6. Access to an external escape routeE30FD30
7. Sub-dividing corridors between alternative exits, or dead ends from the restE20 SaFD20S
8. Door within a cavity barrierE30FD30
9. Protected entrance hall or landing in a flatE20FD20
10. Place of special fire hazard; ancillary accommodation in care homesE30FD30
11. House: to integral garage / protected stair / other fire-resisting constructionE30 Sa / E20 / E20FD30S / FD20 / FD20

Where the door follows the wall or floor, the period comes from Table B2, which sets 30, 60, 90 or 120 minutes by building use and height; that is where most FD60, FD90 and FD120 doors come from. Other Appendix C points shape the specification:

  • Test evidence (C4) must apply to the complete installed assembly: small differences in detail can significantly affect the rating
  • All fire doorsets should be self-closing (C5), except doors to cupboards, to service ducts normally locked shut, and within flats and houses
  • A door that must stand open can be held on an automatic release linked to the fire alarm, a door closer delay device or, except on escape routes, a fusible link (C6)
  • Hinges not tested with the doorset should have a melting point of at least 800 °C (C10)
  • Doors need "Fire door keep shut", "Fire door keep locked shut" or "Automatic fire door keep clear" signs to BS 5499-5 on both sides, with exemptions including doors to and within flats and houses (C11, C12)
  • Doors that divide corridors on escape routes, and doors that swing both ways, should have vision panels (Volume 2, para 5.14)

Glazed fire doors: how much glass is allowed

In a glazed steel or aluminium fire door the glass is part of the tested doorset, so the glass type, pane size, beads and seals must all match the test evidence. Non-insulating fire-resistant glass gives E and some EW ratings; insulating glass with intumescent interlayers or gel gives EI. Two separate limits then decide how much glass a door can have. The first is the doorset's own test evidence, or a formal extended application of it, which sets the maximum pane sizes for each classification: an EI door can only have as much insulating glass as its evidence covers. The second is Table B3 of Approved Document B, which limits uninsulated glass in door leaves on escape routes:

  • Between residential or sleeping accommodation and a common escape route: none
  • Between a protected stairway and the accommodation, or a corridor that is not a protected corridor: 25% of the door area with a single stair, 50% with more than one
  • Between a protected stairway and a protected lobby or corridor, or between accommodation and a protected lobby or dead-end protected corridor: unlimited above 100 mm from the floor
  • Beside an external escape route: unlimited above 1,100 mm from the floor

These limits do not apply to glazing that meets the insulation criterion, which is why an EI door with insulating glass is the usual answer when a door needs more glass. Table B3 also asks for fire-resisting glass to be marked with the manufacturer's and product names, and safety glazing is covered by Approved Document K. Where the door sits in a glazed wall, the fire rated screen needs its own evidence, and so does the joint between the two.

The 2029 change: BS 476 removed from Approved Document B

From 2 September 2029, the 2029 amendments to Approved Document B remove the BS 476 classes for fire resistance in England, leaving European classification as the only route. The new Table C1 drops the BS 476-22 column and gives ratings such as "30 minutes Sa", met by testing and classification to BS EN 13501-2 or by an assessment following paragraphs B1 to B5. Smoke control must match the Sa classification to BS EN 1634-3, so the BS 476-31.1 route goes too. BSI says BS 476-22 has been superseded by BS EN 1634-1 and will be withdrawn on the same date.

The current edition still applies where a building notice, initial notice or full plans application was made before 2 September 2029 and the work is sufficiently progressed before that day or within six months of it. For a new building that means concrete for the permanent foundations, or permanent piling, has started.

  • If a project could be submitted after September 2029, specify European classes (E30 Sa, EI30) and ask for BS EN 1634-1 and BS EN 13501-2 evidence now
  • Ask each supplier which classification its evidence gives: a door with only BS 476-22 evidence cannot simply be relabelled
  • Approved Document B is guidance for building work, so the change does not by itself make installed doors non-compliant. The Home Office says there is no requirement to replace a fire door simply because it does not meet the current Building Regulations standard if it remains in full working order, though it must still be checked and maintained

Fire door certification and labelling

Approved Document B says tests and assessments should be carried out by organisations with the necessary expertise, such as laboratories accredited by UKAS for the test standard. Many doorsets are also covered by third-party certification: an independent certification body checks the factory and the scope of the evidence, and each certified door carries a label or mark that traces it to the certificate. Installer schemes do the same for fitting. Certification is not legally required for every door, but it is the simplest way to show that the door on site is the door that was tested. Ask for the classification report or assessment covering your sizes, glass and hardware, the certificate if there is one, the installation instructions and the hardware schedule, since hinges, closers, locks and exit devices are part of the tested assembly.

Maintenance and the Fire Safety (England) Regulations 2022

A fire door only performs as tested if it closes fully and latches, with its seals, hinges, glass and beads intact. The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to keep fire safety equipment and devices in efficient working order and good repair. In blocks of flats with storeys over 11 m, regulation 10 of the Fire Safety (England) Regulations 2022, in force since 23 January 2023, adds quarterly checks of all fire doors in the common parts, including self-closers, and best-endeavours annual checks of flat entrance doors. Residents in buildings with two or more flats must be told why fire doors matter when they move in and every year. For metal doorsets, Approved Document B points to the DSMA code of practice.

Glazed fire doors from BDF Architectural

BDF Architectural supplies and installs glazed fire rated doors in aluminium and steel for commercial, education, healthcare and high-rise residential buildings, including Jansen Janisol 2 steel doors tested to EI30 and Jansen-Economy 50 and 60 for further slim steel configurations. The rating for each door is set by the fire strategy and checked at technical review against the system's test evidence. Doors in glazed walls can be supplied with matching fire rated screens from our wider fire rated glazing range. If your schedule includes sliding doors, our guide to fire rated sliding doors explains how they are tested and where they can be used.

Frequently asked questions

What does FD30 mean on a fire door?

FD30 means the doorset kept its integrity, stopping flames and hot gases, for 30 minutes in a BS 476-22 fire test. FD30S means it also restricts cold smoke. The European class for the same criterion is E30, or E30 Sa, but it comes from a different test, so one cannot be assumed from the other.

What is the difference between E30 and EI30 fire doors?

Both keep their integrity for 30 minutes. An EI30 door also limits the temperature rise on the protected face, while an E30 door can get hot on that side. Approved Document B rates doors by integrity, but EI doors are used where the fire strategy needs the protected side kept cool, or where uninsulated door openings would exceed 25% of a compartment wall's length.

What is a 1 hour fire rated door?

A doorset rated FD60 under BS 476-22, or E60 (EI60 if insulated) under BS EN 13501-2, meaning it kept its integrity for 60 minutes in a fire test. Approved Document B asks for at least 60 minutes for a door in a compartment wall separating buildings, and for doors in other compartment walls that need 60 minutes.

Where are 90 minute fire doors needed?

Mainly in compartment walls or floors that need 90 minutes. Table C1 rates a door in most compartment walls the same as the wall, and Table B2 sets 90 minutes for some buildings, such as offices without sprinklers whose top floor is more than 18 m and up to 30 m above ground. A door in a wall enclosing a protected shaft can be half the wall's period, with a 30 minute minimum.

Do 2, 3 and 4 hour fire doors exist?

Yes. BS EN 13501-2 has door classes up to 240 minutes, and 2 hour doors (FD120 or E120) are used in 120 minute compartment walls. Approved Document B Table B2 sets minimum periods of no more than 120 minutes, so 3 and 4 hour doors usually come from a fire engineered design, an insurer or another requirement.

What does Sa mean on a fire door rating?

Sa means the doorset restricts smoke leakage at ambient temperature (cold smoke) when tested to BS EN 1634-3. Approved Document B asks for it on doors to protected stairs, lobbies and corridors, as in E30 Sa. S200 is a higher class also tested at 200 °C. The British Standard equivalent is the S in FD30S.

Will FD30 fire doors still be accepted after 2029?

For new building work in England, Approved Document B gives European classes only from 2 September 2029, unless the transitional rules keep a project on the current edition. A door with only BS 476-22 evidence will then need European test evidence or a valid assessment. The change does not by itself require installed doors to be replaced, but they still need inspecting and maintaining.

How much glass can a fire door have?

As much as the doorset's test evidence covers for its classification. Where the glass is uninsulated, Approved Document B Table B3 also limits it on escape routes: none between sleeping accommodation and a common escape route, and 25% or 50% of the door area between a protected stair and the accommodation. Glass that meets the insulation criterion is not limited by Table B3.

How often should fire doors be checked in a block of flats?

Where a block of flats in England has storeys over 11 m, regulation 10 of the Fire Safety (England) Regulations 2022 requires quarterly checks of fire doors in the common parts and best-endeavours annual checks of flat entrance doors. In any building, fire doors must be kept in efficient working order and good repair under the Regulatory Reform (Fire Safety) Order 2005.