In England, Building Regulations require safety glass, or one of a few accepted alternatives, in "critical locations": glass in a door up to 1500 mm above the floor, glass within 300 mm of either edge of a door up to 1500 mm, and any other glass in a wall, window or partition within 800 mm of the floor. The requirement is K4 of the Building Regulations 2010, explained in Section 5 and Diagram 5.1 of Approved Document K (2013 edition). In practice it means toughened or laminated glass in almost every glazed door, bifold and sliding door, and in low windows. Part K is under review, and the call for evidence closes on 11 January 2027.
| What Approved Document K says | |
|---|---|
| Glass in a door | A critical location if it is within 1500 mm of floor level (Diagram 5.1) |
| Glass beside a door | A critical location if it is within 300 mm of either edge of the door and within 1500 mm of floor level |
| Glass in windows, walls and partitions | A critical location if it is within 800 mm of floor level |
| What glass in a critical location must do | Break safely, be robust, be in small panes, or be permanently protected by a screen (para 5.2) |
| Glass that breaks safely | Class 3 of BS EN 12600 (or Class C of BS 6206); for a pane wider than 900 mm in a door or door side panel, Class 2 (or Class B) (para 5.4) |
| Small panes | Up to 250 mm wide and 0.5 m², in annealed glass at least 6 mm thick, or 4 mm in traditional leaded or copper lights (paras 5.6 and 5.7) |
| Permanent screen | Stops a 75 mm sphere touching the glass and is robust (para 5.8) |
| When the rules apply | New glazing and replacement of a whole window or door, frame and glass; not new glass in an existing frame (para 0.2) |
Where is safety glass required? The three critical locations
Approved Document K calls the places where people are most likely to walk into glass critical locations: in and around doors, where hands and arms are at risk, and low in walls and partitions, where children are most at risk. Diagram 5.1 applies to all buildings, homes and commercial premises alike, and to internal doors and partitions as well as outside walls. It shows three zones:
- Doors: any glass in a door that is within 1500 mm of floor level
- Beside doors: glass within 300 mm of either edge of a door, up to 1500 mm above floor level. Diagram 5.1 draws this zone by distance from the door, so building control normally treats a separate window in that strip the same way as a side panel
- Walls, windows and partitions: any other glass within 800 mm of floor level
A pane counts if any part of it falls inside a zone: Diagram 5.1 lists a door pane that only dips below the 1500 mm line as a critical location. Glass outside the zones, such as a fanlight above a door or a window with its glass wholly above 800 mm and away from doors, is shown as non-critical.
Safety glass checker
Does this pane need safety glass?
Pick where the glass is and enter its measurements in millimetres. The answer uses the critical locations in Approved Document K (England).
Yes: this pane needs safety glass
The rule: Glass in a door between floor level and 1500 mm is in a critical location. A pane counts if any part of it is inside the zone. (ADK para 5.1, Diagram 5.1, panes 5 and 8)
What the glass must meet: Glass that breaks safely to Class 3 of BS EN 12600 (or Class C of BS 6206), such as toughened or laminated safety glass. (ADK para 5.4a)
Other ways to comply
- Permanent screen: a robust screen that stops a 75 mm ball touching the glass (and is hard to climb if it guards a drop) means the glass itself doesn’t have to comply. (ADK para 5.8, Diagram 5.4)
This is a guide, not a compliance check: your building control body decides.
Source: Approved Document K: protection from falling, collision and impact (2013 edition, gov.uk), Section 5 and Diagram 5.1. Applies in England.
What counts as safety glass: BS EN 12600 classes
In a critical location, glass must do one of three things: break safely if it breaks, be robust enough not to break (or be in small panes), or be permanently protected (paragraph 5.2). Most doors and low windows take the first route, safety glass. Approved Document K defines a safe break by an impact test to BS EN 12600: the break is safe if it leaves only a small clear opening with small detached particles, if the glass disintegrates into small particles, or if it breaks into separate pieces that are not sharp or pointed (paragraph 5.3).
Paragraph 5.4 says glass is suitable for a critical location if it meets Class 3 of BS EN 12600, or Class C of the older BS 6206. For a door or door side panel with a pane wider than 900 mm, it gives Class 2 of BS EN 12600 (or Class B of BS 6206), a higher impact class.
BS EN 12600 is a pendulum test, and the result is written as a code such as 1(C)2 or 1(B)1. The first number is the highest drop the glass passed: Class 3 is 190 mm, Class 2 is 450 mm and Class 1 is 1200 mm, so a lower number means a tougher test. The letter shows how it broke: A is typical of ordinary annealed glass, B of laminated glass and C of toughened glass. The last number is a second drop-height class judged on a stricter pass test.
Toughened glass (BS EN 12150)
Thermally toughened safety glass is covered by BS EN 12150: Part 1 defines and describes it, and Part 2 is the product standard. Toughening is a heat treatment that makes the glass much stronger than ordinary glass of the same thickness (Pilkington describes its toughened glass as up to five times stronger), and if it does break it shatters into small, relatively harmless pieces. It is the usual choice for doors, side panels and low windows.
Laminated glass (BS EN 14449)
Laminated glass is two or more layers of glass bonded with plastic interlayers such as PVB. Its product standard is BS EN 14449. When it breaks, the fragments stay stuck to the interlayer, which helps the pane hold together. Note that ordinary wired glass is not safety glass, as council building control guidance points out.
The exceptions: robust glass, small panes and screens
Safety glass is the usual answer, but Approved Document K accepts three alternatives in a critical location.
- Robust materials (paragraph 5.5): polycarbonates and glass blocks are inherently strong, and annealed (ordinary) glass gains strength with thickness. Diagram 5.2 sets thickness and size limits for large annealed panes in shop, showroom and office fronts
- Small panes (paragraphs 5.6 and 5.7): an isolated pane, or one of several held in glazing bars or traditional leaded or copper lights, can be annealed glass if it is no more than 250 mm wide and 0.5 m² in area and at least 6 mm thick. In traditional leaded or copper lights, 4 mm glass is acceptable where fire resistance is not important
- Permanent screens (paragraph 5.8): if a permanent screen protects the glass, the glass itself does not need to meet K4. The screen must stop a 75 mm sphere touching the glass and be robust, and if the glass is there to stop people falling, the screen must be hard to climb, for example with no horizontal rails
When the safety glass rules apply: new and replacement glazing
Paragraph 0.2 of Approved Document K says that new glazing where there was none before, as part of building, extending or materially altering a building, is building work, and so is replacing a whole unit, frame and glass. Both must meet K4. Replacing just the glass in an existing frame, for example after a breakage, is not building work, although the supply of the glass may be covered by consumer protection law.
An external window or door is a controlled fitting, so a replacement must be signed off either by an installer registered with a competent person scheme, who certifies the work, or by a building control body. Safety glass in critical locations is one of the things that sign-off covers.
How safety glass is marked
Approved Document K does not itself say how safety glass should be marked. Building control guidance from councils, such as Lancaster City Council's guidance note, says safety glazing should be permanently marked to show the standard it meets, with the mark still visible once the glass is fitted and the beads and pointing are complete, and that in double glazing the rules apply to both panes.
If you are buying new doors or windows, ask the supplier to confirm on the quote which panes are safety glass and to which class, and check the marks before the installer leaves. If an existing pane in a critical location has no mark, treat it as ordinary glass unless the supplier's paperwork shows otherwise.
Bifold, sliding and French doors, side panels and low windows
- Bifold doors: every glazed leaf runs down towards the floor, so its glass is always within 1500 mm of floor level and always a critical location. Check the width of each pane: over 900 mm, paragraph 5.4 gives Class 2
- Sliding and patio doors: the same rule, and sliding door leaves can be large (the Schüco ASS 70.HI takes leaves up to 3000 mm wide), so the 900 mm point often applies
- French doors and single glazed doors: critical up to 1500 mm, including the door pane itself and any glass in the frame beside it
- Side panels and fixed lights next to a door: critical if any part is within 300 mm of the door edge and below 1500 mm. The zone is set by distance, so a fixed light in its own frame is normally treated the same way; check with building control
- Low windows, floor-to-ceiling windows and glass walls in extensions: any glass within 800 mm of the floor is critical, including fixed panes beside a set of bifold or sliding doors
- Glass in internal doors and partitions: Diagram 5.1 covers internal walls too, so a glazed internal door or screen follows the same zones
Our external bifold doors, aluminium sliding patio doors and aluminium French doors are glazed with toughened safety glass, as each product page sets out. For the full set of rules a new door has to meet, including the Part L U-value and sign-off, see bifold doors and Building Regulations, and compare systems in our bifold doors and sliding doors ranges.
Shops, offices and other commercial buildings
The same critical locations apply to commercial buildings. Shopfronts, office entrances and glazed screens also have to meet requirement K5.2, which does not apply to homes: large uninterrupted areas of clear glass in critical locations need permanent manifestation so people can see them. Section 7 asks for marks at two levels, within 850 mm to 1000 mm and 1400 mm to 1600 mm above the floor, unless the glass is already made obvious by features such as mullions, transoms, door framing or large handles. For shopfronts, our guide to shopfront Building Regulations sets out manifestation alongside the other rules and consents that apply.
Do roof lanterns and rooflights need safety glass?
Approved Document K's critical locations are about glass in walls, doors and partitions; Section 5 does not deal with overhead glazing. Rooflights appear elsewhere in the document only for other reasons, such as guarding around openings in roofs. Glass in roof lanterns and rooflights is specified to British Standards for overhead glazing and the maker's guidance.
This is one area the review may touch. In January 2026 the Rooflight Association said laminated glass should be the first choice for the inner pane of a rooflight, so that broken glass stays bonded rather than falling, and that it wants a laminated inner pane to become a requirement in Building Regulations guidance, ideally Approved Document K. If you are choosing a roof lantern, ask which glass the inner pane uses.
Glass balustrades and Juliet balconies
Glass used as guarding, such as a glass balustrade or a Juliet balcony, falls under a different requirement, K2 (protection from falling). Approved Document K sets minimum guarding heights in Diagram 3.1: in a house, 900 mm for stairs, landings and the edges of internal floors, 1100 mm for external balconies, including Juliet balconies, and the edges of roofs, and 800 mm at opening windows. Guarding must resist the loads in BS EN 1991-1-1 with its UK National Annex and PD 6688-1-1, and where it is glass, Section 5 applies too (paragraph 3.2), so a glass balustrade is designed for load as well as safe breakage.
Part K is under review: have your say by 11 January 2027
The Building Safety Regulator opened a call for evidence on Part K and Approved Document K on 19 October 2026. On 17 November it extended it from 10 to 12 weeks, and it now closes on Monday 11 January 2027. It covers all of Part K, including glazing, windows, doors and gates, and guarding. It is not proposing policy changes yet: the aim is to gather evidence and set priorities for future work. Anyone can respond, from professionals and organisations to building owners, occupants and members of the public.
- Online: the call for evidence survey takes 10 to 45 minutes, and you can skip questions
- Email: PartKCfE@buildingsafety.gov.uk
- Post: Review of Part K: Call for Evidence, Technical Policy Team, Building Safety Regulator, 10 South Colonnade, Canary Wharf, London, E14 4PU
- Written responses must name the questions answered, say whether you respond for yourself or an organisation, and give full contact details
If you fit, specify or live with glazing, points you might raise include: the safety glazing guidance moved from Approved Document N into Approved Document K in 2013 with no new technical requirements, and the 2013 edition is still the current one; paragraph 5.4 still refers to BS 6206 alongside BS EN 12600; and overhead glazing such as roof lanterns is not covered by Section 5.
Frequently asked questions
Where is safety glass required by Building Regulations?
In England, Approved Document K treats three zones as critical locations: glass in a door within 1500 mm of the floor, glass within 300 mm of either edge of a door and within 1500 mm of the floor, and any other glass in a wall, window or partition within 800 mm of the floor. Glass there must break safely, be robust or in small panes, or be protected by a permanent screen. In practice that usually means toughened or laminated safety glass.
Do all windows need safety glass?
No. A window only needs safety glass if part of its glass is within 800 mm of the floor, or if it is within 300 mm of the edge of a door and below 1500 mm. Glass wholly above 800 mm and away from doors is not a critical location under Approved Document K.
Does glass in internal doors need to be safety glass?
Approved Document K applies its critical locations to internal walls and doors as well as external ones, so glass in an internal door within 1500 mm of the floor, and glass in an internal screen within 800 mm of the floor, is in a critical location. Ask your building control body whether your particular work needs approval.
Do I need safety glass when replacing a broken pane?
Replacing only the glass in an existing frame is not building work under Approved Document K, so building control sign-off is not needed, although the supply of the glass may be covered by consumer protection law. If the pane is in a critical location, fitting safety glass is still the sensible choice. Replacing the whole window or door, frame and glass, is building work and must meet the safety glass rules.
How can I tell if glass is safety glass?
Look for a permanent mark on the pane. Council building control guidance says safety glazing should be permanently marked to show the standard it meets, and that the mark should still be visible after fitting. A BS EN 12600 class is written as a code such as 1(C)2, where the letter C indicates glass that breaks like toughened glass and B like laminated glass. Ordinary wired glass is not safety glass.
Do both panes of a double glazed unit need to be safety glass?
Approved Document K talks about glazing and does not split a sealed unit into panes, but council building control guidance says that for double glazing the safety glass rules apply to both panes. Ask your supplier to confirm on the quote that both panes of any unit in a critical location are safety glass.
Do roof lanterns need toughened or laminated glass?
The critical locations in Section 5 of Approved Document K cover glass in walls, doors and partitions, not overhead glazing. Glass in roof lanterns and rooflights is specified to British Standards for overhead glazing and the maker's guidance. The Rooflight Association recommends a laminated inner pane as the first choice, so that broken glass stays bonded rather than falling.
What is the Part K call for evidence and when does it close?
It is a Building Safety Regulator call for evidence on Part K and Approved Document K, which cover protection from falling, collision and impact, including glazing, windows, doors and guarding. It opened on 19 October 2026 and closes on 11 January 2027. You can respond through the online survey on the Building Safety Regulator consultation site, by email to PartKCfE@buildingsafety.gov.uk, or by post.
Sources and further reading
- Approved Document K: protection from falling, collision and impact, 2013 edition (GOV.UK)
- Approved Document K, PDF: Section 5, protection against impact with glazing (GOV.UK)
- Have your say on the future of Part K of the building regulations (Building Safety Regulator, GOV.UK)
- Part K call for evidence: how to respond (Building Safety Regulator)
- Doors and windows: Building Regulations (Planning Portal)
- BS EN 12600: pendulum impact test and classification for flat glass (BSI)
- BS EN 12150-2: thermally toughened safety glass, product standard (BSI)
- BS EN 14449: laminated glass and laminated safety glass, product standard (BSI)
- Guardian GlassTime technical manual: EN 12600 classes (Guardian Glass)
- Safety glazing: where is it needed? Building control guidance note 04 (Lancaster City Council)
- The Rooflight Association promotes laminated glass as first choice for overhead glazing (Specification Online, January 2026)