Most problems with existing curtain walling start in the parts that wear, not in the aluminium frame: seals, gaskets and silicone, the insulated glass units, blocked drainage, tired finishes and vent hardware. These can usually be repaired or replaced in the existing frame, and full replacement is normally worth it only when the frame itself performs badly or the building is being upgraded. BDF Architectural is a curtain walling contractor and wrote this guide, so it is a contractor's view. Regulatory points apply to England, with sources at the end.
How curtain walling ages and what fails first
The mullions and transoms are rarely the first thing to go. The parts that wear are the ones that are exposed, soft or moving:
- Seals, gaskets and silicone: the outer seal takes the weather. CWCT notes that a single outer seal is exposed to weathering and prone to failure through accelerated ageing or poor workmanship. Gaskets shrink and harden and open up at corners, and silicone joints at interfaces split or lose adhesion
- Insulated glass units: when the edge seal of a double or triple glazed unit fails, moisture gets into the cavity and the unit mists between the panes. It cannot be cleaned out, so the unit is replaced
- Drainage paths: in a drained system, water that gets past the outer seal should be caught and drained back to the outside. Dirt, debris or stray sealant in the drainage slots stops that, and the water finds its way in instead
- Finishes: powder coated and anodised faces fade, chalk or mark over time, and damage to the coating exposes the metal
- Vent hardware: hinges, stays, locks and vent gaskets wear with use. A vent that drops or no longer closes tight lets in air and water
Design matters too. CWCT describes drained envelopes as far more robust than face-sealed ones, where failure of the single outer seal always lets water in.
Signs of trouble with existing curtain walling
- Water staining or drips at transoms, sills or the slab after rain
- Misting between the panes of a glass unit
- Draughts at joints and vents, or condensation on inner frames
- Gaskets shrunk back from corners, cracked glass, or vents that stick
| Symptom | Likely cause | Usual fix |
|---|---|---|
| Water inside at a transom or sill after rain | Blocked drainage, a failed outer gasket or corner seal | Clear the drainage, re-seal the corners or re-gasket the bay, then water test |
| Water at the head or where the wall meets brickwork or the roof | Failed sealant or flashing at the interface | Cut out and re-seal the joint, repair the flashing |
| Misting between the panes | Failed edge seal on the glass unit | Replace the glass unit |
| Draughts at joints or vents | Shrunk or missing gaskets, worn or badly adjusted vent hardware | Re-gasket, adjust or replace the hardware |
| Condensation on inner frames | High indoor humidity, or a frame with a poor or no thermal break | Check ventilation first; if the frame is the cause, consider replacement |
| Cracked glass | Impact, thermal stress, or glass touching the frame | Replace the glass and check the setting blocks and edge clearances |
| Faded or chalking finish | Weathering of the coating | Clean, repair or recoat, or replace cover caps |
Curtain walling maintenance: a planned regime
Curtain walling needs planned maintenance, not just a response to leaks. Start from the building's operation and maintenance information, then build a regular check into the façade cleaning cycle, when access is already in place:
- Clean the frames as well as the glass, and check that drainage slots are clear
- Inspect external gaskets, corner joints and perimeter silicone for shrinkage, splits and loss of adhesion
- Open and close every vent, and check the hardware, fixings and vent gaskets
- Log misted units and cracked glass by elevation, floor and bay
- Photograph what you find, so a pattern of local faults or a wider problem shows up over time
Diagnosing a curtain wall leak
Find the entry point before resealing anything. Water seen inside may have travelled along a transom or down a mullion from somewhere else, so sealing where it appears often fails. A controlled water test traces it.
CWCT says workmanship is checked using a hose test, while design is tested with a cabinet test or, for patent glazing and rainscreens, a spray bar test. All of these are described in CWCT Technical Note TN41, and CWCT has published a further technical update on site hose testing. Site testing is no substitute for laboratory testing of a design, but it is the practical way to trace a leak. Ask for the method to be named in the report, test one area at a time, and repeat the test after the repair.
Curtain wall refurbishment options: repair, re-glaze, re-gasket or replace
Local repair
Clearing drainage, re-sealing corners and interfaces, and adjusting or replacing vent hardware. It costs least and disturbs least, but it does not change the thermal performance of the wall.
Replacing double glazed units and gaskets in curtain walling
Glass units and gaskets can usually be replaced in the existing frame. On a capped system the glass is clamped by a pressure plate and cover cap, which come off to release the unit. On a structurally glazed system the glass is bonded to the frame with structural silicone, so a new unit has to be bonded in again. Replacement units must suit the frame's glazing depth, and new gaskets must fit the existing profiles, so identify the system first and check that parts are still available. New units can use better glass than the originals, but the frame still limits how much the whole wall improves.
Partial replacement
Replacing one elevation, a stair core or the worst bays deals with the problem where it is. The joints between new and old need careful detailing, and matching sightlines and finish is harder with a different system.
Over-cladding or full replacement
Over-cladding adds a new skin in front of the existing wall. It avoids stripping out the old wall, but it adds load to the structure and fixings and changes the line of the façade. Full replacement costs most and disrupts most, but it is the way to fix failing frames or poor thermal performance, for example with thermally broken curtain walling. Our curtain walling specification guide covers system choice.
Building Regulations when replacing curtain walling
In England, Approved Document L Volume 2 covers buildings other than dwellings. Its Table 4.1 sets a limiting U-value of 1.6 W/m²K for new or replacement curtain walling in existing buildings. Where whole window or door units are replaced (controlled fittings), paragraph 10.3 says they should be draught-proofed, meet Table 4.1 and have insulated cavity closers where appropriate. A 2026 edition takes effect on 24 March 2027, or 24 September 2027 for higher-risk building work, and keeps the 1.6 W/m²K figure, so check which edition applies to your project. Where the curtain walling serves dwellings, Approved Document L Volume 1 applies instead, and it sets 1.4 W/m²K or Window Energy Rating band B for windows, including curtain walling.
The new work must itself meet the applicable requirements, including B4 on external fire spread (regulation 4(1)). Under regulation 3, an alteration is material if it would leave the building not complying with requirements such as B3 (internal fire spread) or B4 (external fire spread) where it did before, or more unsatisfactory where it already fell short. Regulation 4(3) requires the building to comply after the work, or be no more unsatisfactory than before. Slab-edge fire stopping and cavity barriers disturbed by the work need to be reinstated.
Regulation 7(2) applies to relevant buildings: those with a storey at least 18 metres above ground that contain dwellings, an institution or a room for residential purposes. Materials that become part of the external wall must be class A2-s1, d0 or A1. Regulation 7(3) exempts some items, including window frames and glass, and seals, gaskets, fixings, sealants and backer rods, but Approved Document B Volume 2 says spandrel and infill panels must comply. In other buildings with a storey 18 metres or more above ground, Approved Document B Volume 2 (paragraph 12.6) says insulation and filler materials in the external wall, including spandrel panel cores, should be class A2-s3, d2 or better. In buildings with a residential purpose (purpose groups 1 and 2, such as flats, hotels and hospitals) with a storey 11 metres or more above ground, paragraph 12.7 raises this to class A2-s1, d0 or better. Where the façade must resist fire, see fire-rated curtain walling.
Refurbishing curtain walling on an occupied building
Most office refurbishment happens with the building in use. We usually phase the work by elevation and floor, so each area is handed back before the next starts. Agree these points before the programme is fixed:
- Phasing: which elevations, floors or zones go in which order, and how tenants move around the work
- Weathering: how each opening is made weathertight at the end of every shift
- Access: scaffold, mobile platforms, mast climbers or the building's cleaning access
- Working hours, noise, security and deliveries on an occupied site
- Programme: order dates for glass and coatings, and when each phase starts and finishes. See our guide to choosing a curtain walling contractor
Frequently asked questions
Can you replace a double glazed unit in curtain walling?
Usually, yes, without removing the frame. On a capped system the cover cap and pressure plate come off to release the unit. On a structurally glazed system the new unit is bonded in with structural silicone. The new unit must suit the frame's glazing depth.
Why is my curtain wall leaking?
The usual causes are failed outer seals or gaskets, blocked drainage paths and failed sealant where the wall meets other parts of the building. Water can travel inside the frame, so trace the entry point with a controlled water test before resealing.
Can curtain wall gaskets be replaced?
Yes. Gaskets can be replaced bay by bay, using gaskets that fit the existing profiles. Identify the system first and check that the parts are still available, especially on older walls.
Do Building Regulations apply when replacing curtain walling?
In England, yes. Approved Document L Volume 2 sets a limiting U-value of 1.6 W/m²K for replacement curtain walling in buildings other than dwellings (1.4 W/m²K or Window Energy Rating band B where it serves dwellings), the new work must itself meet the fire safety requirements, and on relevant buildings regulation 7(2) controls the materials in the external wall.
Should I repair or replace curtain walling?
Repair or re-glaze when the frames are sound and the faults are local. Consider partial or full replacement when frames are failing, leaks recur across whole elevations or the thermal performance needs a step change.
Sources and further reading
- Approved Document L: conservation of fuel and power, Volume 2 (GOV.UK)
- Approved Document B: fire safety, Volume 2 (GOV.UK)
- The Building Regulations 2010, regulation 3: meaning of building work (legislation.gov.uk)
- The Building Regulations 2010, regulation 4: requirements relating to building work (legislation.gov.uk)
- The Building Regulations 2010, regulation 7: materials and workmanship (legislation.gov.uk)
- CWCT: construction and site testing
- CWCT: building envelope performance
- CWCT: technical updates, including TU24 Site hose testing